Form Number.: 7-3005 File Name: SG Automation Output Revision/Date: 01/May 3, 2005
Department: Engineering
Division: Embedded Software Form Template Owner: Jeff Cougler
18
4.6 ADT Pulse Extended Protocol (e)
eRRLLLsssssssEEEEEEEEE[DC4]
Where, e : Protocol ID.
RR : Virtual Receiver number.
LLL : Virtual Line number.
s : Space Character.
EEEEEEEEE : 7 or 9 digits of data. If less than 9, trailing spaces.
[DC4] : Terminator, 14 Hex.
4.7 SIA Protocol (S)
SRRLLL[#AAAAAA|EMMZZZZ/MMZZZZ/MMZZZZ][DC4]
Where, S : SIA protocol 2 identifier.
RR : Virtual Receiver number.
LLL : Virtual Line number.
[ : Beginning Data Delimiter.
# : Account ID Block Code.
AAAAAA : Account ID, maximum six digits.
| : Field Separator.
E : Function Block Code.
MM : Event Code or Modifier.
ZZZZ : Zone Code, User Code, Door or Relay.
/ : Data Code Packet Separator.
] : Ending Data Delimiter.
[DC4] : Terminator 14 hex.
The length of the signal is varying, and it can support the maximum 66-byte data block transmission from the control panel.
When this optional protocol is selected, all SIA information will be sent to the host automation using this protocol.
Example:
The control panel sends:
#1234 NdaMM-DD-YYtiHH:MM:SS/id22/CL/PA31
The receiver will send this signal to the automation as:
SRRLLL[#1234|Nda04-22-94ti16:02:15/id22/CL/PA31][DC4]
4.8 Telephone Number Protocol (4)
4RRLLLAAAAAALLLTTTTTTT[DC4]
Where, 4 : Protocol number.
RR : Virtual Receiver number.