Form Number.: 7-3005 File Name: SG Automation Output Revision/Date: 01/May 3, 2005
Department: Engineering
Division: Embedded Software Form Template Owner: Jeff Cougler
29
4.17 Silent Knight SFSK2 protocol 1 (F)
The DRL2000 will provide two (2) possible outputs to the automation, according to an option value. When the option is
programmed as “02” the automation output will be as follows:
FRRLLLssssAAAAAAYYZZss[DC4]
Where:
F : represents the FSK2 protocol 1 identifier.
RR : virtual receiver number.
LLL : virtual line number.
S : represents spaces.
AAAAAA : the account number. If the account is 4 or 5 digits, the leading “A”s will be replaced by spaces.
YY : represents the event code.
ZZ : represents the zone/user number
s : represents spaces.
Examples of Possible event codes (YY):
YT00 Battery Trouble
YR00 Battery Restore
DOZZ Access left open ID ZZ
DFZZ Access Forced ID ZZ
AT00 System Trouble - AC
DSZZ Access Station ID ZZ
AJ00 System Restore - AC
LT0Z Trouble Phone Line#0Z
ETZZ Expand Trouble Station ID ZZ (ZZ=17-31)
ERZZ Expand Restore Station ID ZZ (ZZ=17-31)
RP00 Automatic Test
RXZZ Manual Test Zone ZZ
CA Automatic Closing
OA Automatic Opening
CLZZ Normal Closing ID ZZ
OPZZ Normal Opening ID ZZ
CFZZ Forced Closing ID ZZ
ORZZ Forced Opening ID ZZ
OTZZ Supervised Opening ZZ
CG0a Closing Area 0a
OG0a Opening Area 0a
DRZZ Access Granted ID ZZ
When the option is programmed as “01”, the automation output will be as follows:
4.18 Silent Knight FSK2 Protocol 2 (C)
CRRLLLssssAAAAAAXYZZss[DC4]
Where:
C : represents the FSK2 protocol 2 identifier.
RR : virtual receiver number.
LLL : virtual line number
S : represents spaces.
AAAAAA : the account number. If the account is 4 or 5 digits, the leading “A”s will be replaced by spaces.
X : represents the event code.
Y : represents the condition code.